Item
|
Centigrade
|
Fahrenheit
|
Both °C and °F readings are available by reading the appropriate buffer memory area.
|
Analog input signal
|
Thermocouple: Type K or J (either can be used for each channel), 4 channels.
|
Rated temperature range
|
Type K
|
-100°C to 1200°C
|
Type K
|
-148°F to +2192°F
|
Type J
|
-100°C to 600°C
|
Type J
|
-148°F to +1112°F
|
Digital output
|
Type K
|
-1000 to 12000
|
Type K
|
-1480 to 21920
|
Type J
|
-1000 to 6000
|
Type J
|
-1480 to 11120
|
12-bit conversion ,save as complement of 2 in 16 bits
|
Resolution
|
Type K
|
0.4°C
|
Type K
|
0.72°F
|
Type J
|
0.3°C
|
Type J
|
0.54°F
|
Overall accuracy
|
±5% full scale + 1°C
Freezing point of pure water 0°C / 32°F
|
Conversion speed
|
(240ms ± 2%) × 4 channels (unused channels are not converted)
|
Note: Grounded thermocouples are not suitable for this module.