Item |
Specification |
Dielectric withstand voltage |
500VAC, 1min
(between all terminals and ground)
|
Analog circuits |
24V DC ± 10%, 55mA
(external power supply from main unit)
|
Digital circuits |
5V DC, 30mA (internal power supply from main unit) |
Voltage/Current Input |
Either voltage or current input can be selected with your choice of input terminal.
Up to four input points can be used at one time.
|
Analog output range |
DC -10V to +10V (input resistance: 200kΩ).
Warning:this unit may be damaged by input voltage in excess of ±15V DC -20mA to +20mA (input resistance:250Ω).
Warning: this unit may be damaged by input currents in excess of ±32mA.
|
Digital input |
12-bit conversion stored in 16-bit 2’s complement form
Maximum value:+2047 Minimum value:-2048
|
Resolution |
5mV (10V default range 1/2000)/20µA (20mA default range 1/1000) |
Over all accuracy |
±1% (for the range of -10V to +10V)/±1% (for the range of -20mA to +20mA) |
Conversion speed |
15ms/channel (Normal speed), 6ms/channel (High speed) |
CE Certification |
CE marked |