| Item |
Specification |
| Dielectric withstand voltage |
500V AC, 1min (between all terminals and ground) |
| Analog circuits |
24V DC ± 10%, 55mA |
| Digital circuits |
5V DC, 90mA (internal power supply from the main unit) |
| Centigrade (°C)/Fahrenheit (°F) |
Both °C and °F are available by reading the appropriate buffer memory(BFM).
|
| Input signal |
Thermocouple: Type K or J (either can be used for each channel), 4 channels
|
| Rated temperature range(°C) |
Type K:-100℃ to +1200℃ Type J:-100℃ to +600℃ |
| Rated temperature range(°F) |
Type K:-148℉to +2192℉ Type J:-148℉ to +1112℉ |
| Digital output(°C) |
Type K:-1000 to 12000 Type J:-1000 to 6000 |
| Digital output(°F) |
Type K:-1480 to 21920 Type J:-1480 to 11120 |
| Digital output |
12-bit conversion ,save as complement of 2 in 16 bits |
| Overall accuracy |
± (0.5% full scale +1°C)
Freezing point of pure water 0°C / 32°F
|
| Conversion speed |
(240ms ± 2%) × 4 channels (unused channels are not converted) |
| CE Certification |